Inspections
Air receiver and compressed air system inspection checklist
The routine check of a compressed air receiver and its system against OSHA 1910.169(b): access to drains and manholes, draining, the pressure gauge, the safety valve and nothing between it and the tank, with a pressure reading and a leak walk.
- How often
- Weekly, or at the interval your site sets
- Who
- Maintenance technician or operator
- Time
- About 10 min
- Items
- 19
Download this checklist
Free, no sign-up
Have your own paper version? A photo of it is enough for Vardian AI to draft the form. Photo-to-form →
Before you use it
- OSHA 29 CFR 1910.169(b) requires every air receiver to be installed so that all drains, handholes and manholes are easily accessible, and never buried underground or located in an inaccessible place; to have a drain pipe and valve at its lowest point, with the receiver completely drained frequently enough to prevent excessive liquid from accumulating; and to have a readily visible indicating pressure gauge and one or more spring-loaded safety valves.
- Under 1910.169(b)(3), the safety valves’ total relieving capacity keeps receiver pressure from exceeding the maximum allowable working pressure by more than 10 percent; no valve of any type is placed between the receiver and its safety valves; safety appliances are installed so that they cannot readily be made inoperative, including by the elements; and all safety valves are tested frequently and at regular intervals. OSHA sets no fixed interval for draining or valve testing, so take both from the manufacturer’s instructions.
- New receivers are built to the ASME Boiler and Pressure Vessel Code, Section VIII, and safety valves are constructed, installed and maintained to it (1910.169(a)(2)). Record the maximum allowable working pressure from the nameplate and set the pressure limits from it.
Receiver
- 1Checkpoint scan
Scan the receiver tag
- 2Pass / fail
Nameplate legible, with the maximum allowable working pressure
- 3Pass / fail
Drains, handholes and manholes easily accessible
- 4Pass / fail
Shell, supports and connections free of visible corrosion, dents and leaks
Gauge and safety valve
- 5Pass / fail
Pressure gauge readily visible and readable
- 6Reading· psi or bar
Receiver pressure
Set the limits from the manufacturer’s manual and your normal operating range.
- 7Pass / fail
Spring-loaded safety valve fitted, with no valve between it and the receiver
- 8Pass / fail
Safety valve and controls not obstructed, gagged or otherwise made inoperative
- 9Pass / fail
Safety valve tested at its scheduled interval
- 10Note
Date of the last safety valve test
Drain
- 11Pass / fail
Drain valve at the lowest point opened and the receiver completely drained
- 12Choice
Liquid drained
None · Normal · Excessive: shorten the drain interval
- 13Pass / fail
Automatic drain trap, where fitted, discharging
System
- 14Pass / fail
No audible air leaks at lines, hoses and fittings
- 15Pass / fail
Hoses and couplings undamaged and secured
- 16Pass / fail
Dryer and filters, where fitted, working and drained
Result
- 17Choice
Result
Safe to operate · Removed from service
- 18Photo
Photo of any defect
- 19Signature
Inspected by
References
Download this checklist
Free, no sign-up
Read more
Field types in this template
- Checkpoint scan
- Pass / fail
- Reading
- Note
- Choice
- Photo
- Signature
In Vardian, readings are checked against their limits as they are entered, and photos and signatures attach to the check itself.
From the sheet to the round
Build a template as a Vardian form, and each line becomes a checkpoint that knows its limit.
Animation: a paper checklist line, compressor discharge pressure with a blank for the reading in bar, becomes a Vardian checkpoint with a limit of 7.0 to 8.5 bar. Scanning the compressor's NFC tag verifies the checkpoint, a reading of 9.1 bar is flagged out of range, and a work order is created from it.
Run this checklist on the round
We'll set it up in Vardian with your checkpoints and limits during a demo.